Introduction

Fail-Safe controllers (e.g., SIMATIC S7-1200/1500) require special F-DI input modules designed for handling signals from safety devices - such as emergency stop buttons, interlocks, light curtains, and limit switches.

In this article, we will cover: the construction and operation of the SM 1226 F-DI module, diagnostic and testing mechanisms, different input configuration methods (1oo1, 1oo2), and how to achieve the appropriate SIL/PL safety levels.

SM 1226 F-DI 16 × 24 V DC Module

SM 1226 F-DI 16-channel safe input module for Siemens S7-1200 Safety

The SM 1226 F-DI module has 16 input channels at 24 V DC designed to work with safety sensors/switches and 3/4-wire proximity sensors (e.g., Siemens BERO).

It complies with EN 61131-2, type 1 and is equipped with two sensor power outputs (each serving up to 8 inputs). This allows building complex safety systems with redundancy.

Structure and Input Configuration

Each F-DI module contains two microprocessors that independently monitor input groups (a.0…a.7 and b.0…b.7).

Available configurations:

  • 16 × 1oo1 (one out of one) → SIL 2 / Cat. 3 / PL d
  • 8 × 1oo2 (one out of two) → SIL 3 / Cat. 3 or 4 / PL e
  • Mixed configurations (some 1oo1, some 1oo2)

1oo2 (one out of two) means that the signal must be consistently detected by two independent inputs (e.g., a.0 and b.0). A discrepancy triggers a safety error.

Diagnostic Mechanisms

The SM 1226 F-DI module has several functions that increase safety:

  • Short-circuit test - momentarily cutting sensor power and checking whether the input signal also drops.
  • Dual monitoring - two microprocessors test their input circuits.
  • Discrepancy error detection - the CPU transitions to the safe state if 1oo2 signals differ for longer than permitted.

SIL/PL Safety Levels

The module's capabilities depend on the sensor connection method. The table below shows what SIL/PL can be achieved:

  • 1oo1, 1 channel → max PL d (SIL 2/3)

  • 1oo2, two equivalent channels → max PL e (SIL 3)
  • 3/4-wire connections → max PL e with additional short-circuit detection

Properly selected sensors and input configuration allow building systems compliant with ISO 13849-1 and IEC 62061 requirements.

F-DI safe input connection examples: 1oo1, 1oo2, 3-wire, 4-wire sensors

Connection Examples

1oo1 - Single Channel

Simple circuits, max PL d.

1oo2 - Single Dual Sensor

Higher safety, redundancy.

1oo2 - Two Independent Sensors

Most commonly used in emergency stop circuits.

1oo2-3-Wire and 4-Wire Sensors

Used with light curtains, scanners, and more complex systems.

Summary

The SM 1226 F-DI module is a key element of safety systems based on SIMATIC S7-1200 controllers. Thanks to its ability to operate in 1oo1 and 1oo2 configurations, dual microprocessor monitoring, and diagnostic tests, it enables meeting high SIL/PL requirements in industrial applications.

👉 Check out our full Safety PLC Course here

Want to master Safety PLC programming? Learn everything from safety principles to real-world configurations in our comprehensive online course.